Multifunctional Electrical Installations Meter Sonel MPI-525
SKU: SL-MPI-525-EU-R1
Multifunction Electrical Installations Meter Sonel MPI-525 can be used for all measurements in commissioning of electrical installations in accordance with applicable regulations.
- Has an option of measuring the insulation resistance with a voltage of 2500 V.
- Copes well in difficult environmental conditions.
Free shipping over 200 EUR
Estimated shipping time 3-4 weeks
Estimated shipping time 3-4 weeks
The Multifunction Electrical Installations Meter Sonel MPI-525 is a versatile and accurate tool that combines the measuring capabilities of several devices in one, making it perfect for commissioning of electrical installations in accordance with applicable regulations.
How to use Multifunction Electrical Installations Meter Sonel MPI-525
The meter is easy to use and offers a wide range of functionalities. It can be used for short circuit loop impedance measurements (also in circuits secured with RCDs), RCD parameter measurements, insulation resistance measurements, earth resistance measurements (3-pole method), continuity of protective and equipotential bondings, and phase sequence tests. Additionally, it can also be used for checking the correctness of PE connection using a contact electrode, measuring voltage (0 … 500 V) and network frequency, and storing up to 990 results for later analysis. Wireless data transmission to a computer is also supported.Features of Multifunction Electrical Installations Meter Sonel MPI-525
Product information | |
---|---|
Product name | Multifunctional Electrical Installations Meter Sonel MPI-525 |
Brand | Sonel |
Fault loop impedance ZL-PE, ZL-N, ZL-L | |
Measurement range | 0,13 - 1999 Ω |
Display range | 0 - 1999 Ω |
Resolution | from 0,01 Ω |
Accuracy ±(%m.v. + digits) | ±(5 % m.v. + 3 digits) |
Fault loop impedance ZL-PE in RCD mode | |
Measurement range | from 0,50 - 1999 Ω |
Display range | 0 - 1999 Ω |
Resolution | from 0,01 Ω |
Accuracy ±(%m.v. + digits) | ±(6 % m.v. + 5 digits) |
General and short-time delay RCD | |
Measurement range | 0 - 300 ms |
Display range | 0 - 300 ms |
Resolution | 1 ms |
Accuracy ±(%m.v. + digits) | ±(2 % m.v. + 2 digits) |
Selective RCD | |
Measurement range | 0 - 500 ms |
Display range | 0 - 500 ms |
Resolution | 1 ms |
Accuracy ±(%m.v. + digits) | ±(2 % m.v. + 2 digits) |
For sinusoidal residual current (AC type) | |
Measurement range | 3,0 mA - 1000 mA |
Display range | 3,0 mA - 1000 mA |
Resolution | from 0,1 mA |
Accuracy ±(%m.v. + digits) | ±5 % IΔn |
For unidirectional residual current and unidirectional with the 6 mA DC bias (type A) | |
Measurement range | 3,5 mA - 700 mA |
Display range | 3,5 mA - 700 mA |
Resolution | from 0,1 mA |
Accuracy ±(%m.v. + digits) | ±10 % IΔn |
For direct residual current (type B) | |
Measurement range | 2,0 mA - 1000 mA |
Display range | 2,0 mA - 1000 mA |
Resolution | from 0,1 mA |
Accuracy ±(%m.v. + digits) | ±10 % IΔn |
Earth resistance - 3-pole method | |
Measurement range | from 0,50 Ω - 1,99 kΩ |
Display range | 0 - 1,99 kΩ |
Resolution | from 0,01 Ω |
Accuracy ±(%m.v. + digits) | from ±(2 % m.v. + 3 digits) |
Insulation resistance - Measuring voltage 50 V | |
Measurement range | 50 kΩ - 250 MΩ |
Display range | 0 kΩ - 250 MΩ |
Resolution | from 1 kΩ |
Accuracy ±(%m.v. + digits) | from ±(3 % m.v. + 8 digits) |
Insulation resistance - Measuring voltage 100 V | |
Measurement range | 100 kΩ - 500 MΩ |
Display range | 0 kΩ - 500 MΩ |
Resolution | from 1 kΩ |
Accuracy ±(%m.v. + digits) | from ±(3 % m.v. + 8 digits) |
Insulation resistance - Measuring voltage 250 V | |
Measurement range | 250 kΩ - 999 MΩ |
Display range | 0 kΩ - 999 MΩ |
Resolution | from 1 kΩ |
Accuracy ±(%m.v. + digits) | from ±(3 % m.v. + 8 digits) |
Insulation resistance - Measuring voltage 500 V | |
Measurement range | 500 kΩ - 2 GΩ |
Display range | 0 kΩ - 2 GΩ |
Resolution | from 1 kΩ |
Accuracy ±(%m.v. + digits) | from ±(3% m.v. + 8 digits) |
Insulation resistance - Measuring voltage 1000 V | |
Measurement range | 1000 kΩ - 3 GΩ |
Display range | 0 kΩ - 3 GΩ |
Resolution | from 1 kΩ |
Accuracy ±(%m.v. + digits) | from ±(3 % m.v. + 8 digits) |
Insulation resistance - Measuring voltage 2500 V | |
Measurement range | 2500 kΩ - 9,99 GΩ |
Display range | 0 kΩ - 9,99 GΩ |
Resolution | from 1 kΩ |
Accuracy ±(%m.v. + digits) | from ±(3 % m.v. + 8 digits) |
Measurement of resistance of protective conductors and equipotential bondings with ±200 mA current | |
Measurement range | 0,12 Ω - 400 Ω |
Display range | 0 - 400 Ω |
Resolution | from 0,01 Ω |
Accuracy ±(%m.v. + digits) | ±(2 % m.v. + 3 digits) |
Measurement of resistance with low current | |
Measurement range | 0 Ω - 1999 Ω |
Display range | 0 - 1999 Ω |
Resolution | from 0,1 Ω |
Accuracy ±(%m.v. + digits) | ±(3 % m.v. + 3 digits) |
Environmental Conditions | |
Ingress protection | IP54 |
Operating temperature | 0 - 50 °C |
Storage temperature | -20 - 70 °C |
Humidity | 20 - 90 % |
Nominal temperature | 23 ± 2 °C |
Reference humidity | 40 - 60 % |
Measuring category acc. to EN 61010 | IV 300 V, III 600 V |
Type of insulation acc. to EN 61010-1 and IEC 61557 | double |
Data Storage | |
Memory | 990 cells, 57 500 records |
Computer Interface | |
Data transmission | USB 2.0, radio |
Dimensions and Weight | |
Dimensions (W x H x D) | 223 x 288 x 75 mm (8,8 x 11,3 x 3,0 in) |
Weight | 2.2 kg (4,9 lbs) |
- WS-03 Adapter with START button with UNI-SCHUKO plug
- AKU-07 NiMH battery 4.8 V 4.2 Ah
- Factory calibration certificate
- L-2 Carrying case
- K-01 Crocodile clip, black, 1 kV, 20 A
- K-09 Crocodile clip, black, 11 kV, 32 A
- K-02 Crocodile clip, yellow, 1 kV, 20 A
- Hanging straps
- Test lead 15 m for earth resistance measurements (on a reel, banana plugs) blue
- Test lead 30 m for earth resistance measurements (on a reel, banana plugs) red
- Test lead 1.2 m CAT III/1000V CAT IV/600V (banana plugs) blue
- Test lead 1.2 m, 1 kV (banana plugs) red
- Test lead 1.2 m CAT III/1000V CAT IV/600V (banana plugs) yellow
- Test lead 1.8 m 5 kV (banana plugs, shielded) black/graphite
- Test lead 1.8 m 5 kV (banana plugs) red
- Mains power cable 230 V (IEC C7 plug)
- USB cable
- Pin probe, blue 1 kV (banana socket)
- Earth contact test probe (rod), 30 cm (2pcs)
- Pin probe CAT III/1000V CAT IV/600V (banana socket) red
- Pin probe 5 kV (banana socket) red
- Pin probe CAT III/1000V CAT IV/600V (banana socket) yellow
- Z-7 Power supply adapter
- MPI-525 meter
Sonel Reports PLUS SonelReader