Empty compare list
Compare list
![]() The Three-Phase Winding Ohmmeter DV Power TWA25A Remove from compare list | |
Winding Resistance Measurement | |
---|---|
Test currents | 5 mA – 25 A DC |
Output voltage | up to 55 V DC |
Measurement range | 0,1 μΩ – 10 kΩ |
Mesurement resolution | 0,1 μΩ – 1 Ω |
Typical accuracy | ± (0,1 % rdg + 0,1 % FS) |
OLTC Dynamic Resistance Measurement | |
Sampling rate | 4 ms |
Open circuit detection and warning | Automatic |
Transition current ripple measurement | Yes |
Transition time measurement | Yes |
Temperature Measurement | |
One temperature measurement channel | Thermometer Pt100 class B |
Mesurement range | -50 °C – +180 °C |
Mesurement resolution | 0.1 °C |
Power Supply | |
Powered by | Mains power |
Mains power connection according to | IEC/EN60320-1 UL498, CSA 22.2 |
Mains power input voltage | 90 V – 264 V AC |
Mains power input frequency | 50/60 Hz |
Input power | 1500 VA |
Data Storage | |
Internal memory positions | 500 |
Storage | USB flash drive feature enables storage of a huge number of measurements |
Computer Interface | |
Interface v1 | USB (standard) |
Interface v2 | RS232 (optional) |
Display | |
Display v1 | LCD screen with 20 characters by 4 lines |
Display v2 | LCD with backlight |
Environmental Conditions | |
Operating temperature | -20 ºC – +55 ºC (-4 ºF – +131 ºF) |
Storage & transportation | -40 ºC – +70 ºC (-40 ºF – +158 ºF) |
Humidity | 0 % – 95 % relative humidity |
Applicable Standards | |
Installation/overvoltage | CAT II IEC/EN 61010-1 |
Pollution | Degree 2 |
Low voltage directive | Directive 2014/35/EU (CE Conform) |
Electromagnetic compatibility | Directive 2014/30/EU (CE Conform) EN 61326-1 |
Dimensions and Weight | |
Dimensions (W x H x D) | 194 x 478 x 389 mm (7,6 x 18,8 x 15,3 in) |
Weight | 12.8 kg (28,2 lbs) |