|   Battery Load Unit DV Power BLU100ARemove from compare list | |
| Internal Voltage Measurement | |
|---|---|
| Measurement range | 0 – 500 V DC | 
| Measurement resolution | 0,1 V or better | 
| Typical accuracy | ± (0,5 % rdg + 0,1 V) | 
| Internal Current Measurement | |
| Measurement range | 0 – 300 A | 
| Measurement resolution | 0,1 A | 
| Typical excitation current accuracy | ± (0,5 % rdg + 0,1 A) | 
| Display range | 0 – 2 999,9 A DC | 
| Time Measurement | |
| Typical accuracy | ± 0,01 % of reading ± 1 digit | 
| Mains Power Supply | |
| Connection according to | IEC/EN60320-1 C320 | 
| Mains supply | 90 – 264 V AC, 50/60 Hz | 
| Input power | 100 W | 
| Fuse | 2 A / 250 V, type F | 
| Input for Current Probe | |
| Range | 0 – 1 V DC | 
| mV/A ratio | Software settable values | 
| Input impedance | > 1 MΩ | 
| Load Section | |
| Battery Voltage | 5,25 – 300 V | 
| Power | 14,2 kW (max) | 
| Discharge modes | Constant current / power / resistance current, power or resistance profile mode | 
| Constant Current (Const I) | |
| Range | 0 – 160 A DC | 
| Resolution | 0,1 A | 
| Typical accuracy | ± (0,5 % rdg + 0,2 A) | 
| Ripple | max 0,4 A peak | 
| Constant Resistance (Const R) | |
| Range | 0 – 300 Ω | 
| Resolution | 0,1 Ω | 
| Typical accuracy | ± 1 % | 
| Constant Power (Const P) | |
| Range | 0 – 14,2 kW | 
| Resolution | 0,01 kW | 
| Typical accuracy | ± 1 % | 
| Ripple | max 0,2 kW peak | 
| Range/Resolution | |
| Current | 0 – 2 999,9 A DC / 0,1 A | 
| Voltage | 0 – 999,9 V DC / 0,1 V | 
| Capacity | 0 – 9999,9999 Ah / 0,0001 Ah | 
| Time | 00 h | 
| Stop Parameters | |
| Stop parameters | End voltage (total battery or per-cell voltage) Capacity Test time | 
| Current Probe Specifications | |
| Current clamp | 30/300 A | 
| Ranges | 30 A and 300 A | 
| mV/A ratios | 10 mV/A and 1 mV/A | 
| Supply | from the instrument | 
| Dimensions and Weight | |
| Dimensions (W x H x D) | 221 x 440 x 355 mm (8,7 x 17,3 x 14,0 in) | 
| Weight | 12.8 kg (28,2 lbs) | 