Battery Load Unit DV Power BLU100A
Remove from compare list
Internal Voltage Measurement
Measurement range 0 – 500 V DC
Measurement resolution 0,1 V or better
Typical accuracy ± (0,5 % rdg + 0,1 V)
Internal Current Measurement
Measurement range 0 – 300 A
Measurement resolution 0,1 A
Typical excitation current accuracy ± (0,5 % rdg + 0,1 A)
Display range 0 – 2 999,9 A DC
Time Measurement
Typical accuracy ± 0,01 % of reading ± 1 digit
Mains Power Supply
Connection according to IEC/EN60320-1
C320
Mains supply 90 – 264 V AC, 50/60 Hz
Input power 100 W
Fuse 2 A / 250 V, type F
Input for Current Probe
Range 0 – 1 V DC
mV/A ratio Software settable values
Input impedance > 1 MΩ
Load Section
Battery Voltage 5,25 – 300 V
Power 14,2 kW (max)
Discharge modes Constant current / power / resistance
current, power or resistance profile mode
Constant Current (Const I)
Range 0 – 160 A DC
Resolution 0,1 A
Typical accuracy ± (0,5 % rdg + 0,2 A)
Ripple max 0,4 A peak
Constant Resistance (Const R)
Range 0 – 300 Ω
Resolution 0,1 Ω
Typical accuracy ± 1 %
Constant Power (Const P)
Range 0 – 14,2 kW
Resolution 0,01 kW
Typical accuracy ± 1 %
Ripple max 0,2 kW peak
Range/Resolution
Current 0 – 2 999,9 A DC / 0,1 A
Voltage 0 – 999,9 V DC / 0,1 V
Capacity 0 – 9999,9999 Ah / 0,0001 Ah
Time 00 h
Stop Parameters
Stop parameters End voltage (total battery or per-cell voltage)
Capacity
Test time
Current Probe Specifications
Current clamp 30/300 A
Ranges 30 A and 300 A
mV/A ratios 10 mV/A and 1 mV/A
Supply from the instrument
Dimensions and Weight
Dimensions (W x H x D) 221 x 440 x 355 mm (8,7 x 17,3 x 14,0 in)
Weight 12.8 kg (28,2 lbs)