Transformer Turns Ratio Tester DV Power TRT03A
Remove from compare list
Turns Ratio Measurement
Test voltages 8 V, 40 V, 100 V AC
Turns ratio measurement range 0,8 – 50 000
Turns ratio resolution 5 digits
Typical accuracy from ± 0,05 % rdg to ± 0,2 % rdg
Excitation Current Measurement
Excitation current range 0 – 2 A
Excitation current resolution 0,1 μA – 100 μA
Typical excitation current accuracy ± (0,25 % rdg + 500 μA)
Phase Angle Measurement
Phase angle range 0 – 360°
Phase angle resolution 0,01°
Typical phase angle accuracy ± 0,05°
Power Supply
Supplied by Mains power
Mains power connection acc. to IEC/EN60320-1
UL498, CSA 22.2
Mains power input voltage 90 – 264 V AC
Mains power input frequency 50/60 Hz
Input power 200 VA
Data Storage
Storage 10 000 internal memory positions
Computer Interface
Interface v1 USB (standard)
Interface v2 RS232 (optional)
Display
Display v1 LCD screen with 20 characters by 4 lines
Display v2 LCD with backlight
Printer (optional)
Printer Built-in printer
Paper width 58 mm (2,3 in)
Environmental Conditions
Operating temperature -20 ºC – +60 ºC (-4 ºF – +140 ºF)
Storage & transportation -40 ºC – +70 ºC (-40 ºF – +158 ºF)
Humidity 0 % – 95 % relative humidity
Applicable Standards
Installation/overvoltage CAT II
IEC/EN 61010-1
Pollution degree 2
Low voltage directive Directive 2014/35/EU (CE Conform)
Electromagnetic compatibility Directive 2014/30/EU (CE Conform)
EN 61326-1
Dimensions and Weight
Dimensions (W x H x D) 194 x 478 x 390 mm (7,6 x 18,8 x 15,4 in)
Weight 8 kg (17,6 lbs)