Transformer Turns Ratio Tester DV Power TRT03A
SKU: TRT03AX-EU-R1
True three-phase and single-phase measurement of three-phase transformer's turns ratio with a voltage up to 100 V AC and additional test voltage of 1 V for current transformers.
- Standard accessories included
- Software included
- Certificate of calibration included
- 3 years warranty
Kostenloser Versand über 200 EUR
Geschätzte Versandzeit 4-5 weeks
Geschätzte Versandzeit 4-5 weeks
As one of the main parts of an electrical substation, a power transformer must be reliable and operative 24 hours a day, 7 days in a week. Proper maintenance of the electrical transformer is beneficial in order to increase safety and detect problems before they become too dangerous. It also helps to reduce maintenance expenses.One of the most important maintenance test of power transformers is the turns ratio test.The DV Power TRT03A is a device that provides the possibility of a turns ratio test with the best turns ratio accuracy of 0.03%. It belongs to the TRT Standard Series, fully automatic test set specially designed for turns ratio, phase shift, and excitation current measurements of a power, distribution and instrument transformers. TRT03A is a lightweight solution that weighs only 8 kg (17.6 lbs) with a single-phase test voltage source. Test voltages of a DV Power's TRT03A are 8, 40 and 100 V AC. Typical applications of the instrument Turns ratio measurement Turns ratio deviation calculation Excitation current measurement Phase angle measurement Automatic vector group detection Verification of demagnetization process Magnetic balance test The DV Power TRT03A is based on a state of the art technology, using the most advanced technique available today. The transformer turns ratio is determined with TRT03A by applying voltages across HV windings, measuring voltages across the unloaded transformer winding and then displaying the ratio of these voltages.For all three parameters measured: turns ratio, excitation current and phase angle, TRT Standard Series has the highest accuracy in the market, which makes potential transformer irregularities and faults more visible. Official DV-Win software is included in the purchase price of the DV Power’s TRT03A. It allows full control of TRT functions, has the option for creating and storing test plans. All test results are presented both, numerically and graphically. Also, with using the DV Win software the results can be arranged, exported and printed for a report.
Produktinformation | |
---|---|
Produktname | Transformer Turns Ratio Tester DV Power TRT03A |
Marke | DV Power |
Herkunftsland | Sweden; |
Turns Ratio Measurement | |
Test voltages | 8 V, 40 V, 100 V AC |
Turns ratio measurement range | 0,8 – 50 000 |
Turns ratio resolution | 5 digits |
Typical accuracy | from ± 0,05 % rdg to ± 0,2 % rdg |
Excitation Current Measurement | |
Excitation current range | 0 – 2 A |
Excitation current resolution | 0,1 μA – 100 μA |
Typical excitation current accuracy | ± (0,25 % rdg + 500 μA) |
Phase Angle Measurement | |
Phase angle range | 0 – 360° |
Phase angle resolution | 0,01° |
Typical phase angle accuracy | ± 0,05° |
Power supply | |
Supplied by | Mains power |
Mains power connection acc. to | IEC/EN60320-1 UL498, CSA 22.2 |
Mains power input voltage | 90 – 264 V AC |
Mains power input frequency | 50/60 Hz |
Input power | 200 VA |
Data Storage | |
Storage | 10 000 internal memory positions |
Computer Interface | |
Interface v1 | USB (standard) |
Interface v2 | RS232 (optional) |
Display | |
Display v1 | LCD screen with 20 characters by 4 lines |
Display v2 | LCD with backlight |
Printer (optional) | |
Printer | Built-in printer |
Paper width | 58 mm (2,3 in) |
Environmental Conditions | |
Operating temperature | -20 ºC – +60 ºC (-4 ºF – +140 ºF) |
Storage & transportation | -40 ºC – +70 ºC (-40 ºF – +158 ºF) |
Humidity | 0 % – 95 % relative humidity |
Applicable Standards | |
Installation/overvoltage | CAT II IEC/EN 61010-1 |
Pollution | degree 2 |
Low voltage directive | Directive 2014/35/EU (CE Conform) |
Electromagnetic compatibility | Directive 2014/30/EU (CE Conform) EN 61326-1 |
Abmessungen und Gewicht | |
Abmessungen (W x H x D) | 194 x 478 x 390 mm (7,6 x 18,8 x 15,4 in) |
Gewicht | 8 kg (17,6 lbs) |
- Cable bag
- Ground (PE) cable
- USB cable
- H winding test cable 5 m, 3~ connection with TTA clamps
- H winding test cable extension, 5 m, shielded
- Mains power cable EU 10 A
- Plastic transport case – medium size
- USB with DV-TR software
- Tap changer control cable 5 m
- TRT03A device
- X winding test cable, 5 m, 3~ connection with TTA clamps
- X winding test cable extension, 5 m, shielded
The software provides numerous advantages, such as downloading test results from the instrument, acquisition of test results, creating graphs for easier analysis, creating test reports and saving them in several different formats. All results are displayed both numerically and graphically, making analysis as easy as possible. Test reports, generated with a single click, can be quickly customized, and directly printed or saved.