Leistungsschalter-Analysator & Zeitgeber DV Power CAT34

SKU: CAT3400-EU-R1

Timing, Coil current, displacement measurement of circuit breakers with one breaking unit per phase.

  • Standard accessories included
  • Software included
  • Calibration certificate included
  • 3 years warranty
Kostenloser Versand über 200 EUR
Geschätzte Versandzeit 4-5 weeks
The CAT34 can be used as a standalone or a PC-controlled digital instrument for circuit breakers condition assessment. It is intended for timing measurement of circuit breakers with one breaking chamber per phase. A variety of operations (such as Open-Close, Open-Close-Open) can be initiated by using the coil control channel or by sensing the breaker’s contact position using the External trigger channel. The CAT34 device senses a voltage across the breaker's coil using the External Trigger. The Auxiliary input channel is used to monitor the 52a and 52b auxiliary contacts. The External trigger channel can be used as a third auxiliary input. The CAT34 can measure the displacement of the circuit breaker using the integrated transducer channel and measure up to two (2) analog signals (current and/ or voltage). If there are any pre-insertion resistors present in the circuit breaker, the device will automatically detect them and measure the resistance using the main contact input channels. The test results can be printed numerically and graphically using the Built-in 80 mm Thermal printer. The thermal printer is listed as part of the optional accessories of the CAT34 unit. Simple & Easy to operate Three (3) timing channels for main and pre-insertion resistors Resistance measurement of pre-insertion resistors Three (3) Auxiliary input channels Two (2) Analog input channels that can be used for voltage and current measurement. One (1) universal transducer channel (Compatible for either linear analog or digital rotary transducer) Trip & Close coils current measurement Test results can be saved directly to a USB Flash Drive The included DV-Win software enables detailed analysis of the test results and complete control of the CAT34 device using the PC
Produktinformation
Produktname Leistungsschalter-Analysator & Zeitgeber DV Power CAT34
Marke DV Power
Main Contact Inputs
Number of contact inputs 3 (3x 1), 1 per phase
Each channel detects main contacts Closed ≤ 10 Ω
Resistor contacts range 10 Ω to 5 kΩ
Open ≥ 5 kΩ
Open circuit voltage 20 V DC
Short circuit voltage 50 mA
Time Measurement
Time measurement resolution 0,1 ms to 10 ms depending on test duration (sampling rate up to 10 kHz)
Time accuracy 0,05% of the reading ± resolution
External trigger Yes, 2 channels (Trigger input voltage 10 V - 300 V AC/DC)
Breaker Operation
Sequences Close (C)
Open (O)
Close-Open (C-O)
Open-Close (O-C)
Open-Close-Open (O-C-O)
DC Voltage Measurement
Range ±0,5 V, ±2,5 V, ±60 V and ±300 V AC/DC
Analog Inputs
Coil current measurement 2 channels
Voltage measurement 2 channels
Transducer Input
Digital transducer inputs 1 channel
Analog transducer inputs 1 channel
Coil Driver
Number of channels 2 (Trip and Close coil)
Driver characteristics ± 300 V DC / AC peak, ±35 A DC to 5 kHz
Timing control Electronic drivers provide superior timing control
Protection Overcurrent and overvoltage protection
Coil supply input ± 300 V DC / AC peak, ±35 A
DC to 5 kHz
Current Measurement
Current measurement for Trip and Close coil, 2 channels, Hall-Effect sensor
Range ±35 A DC to 5 kHz
Accuracy ± (0,5 % rdg + 0,1 % FS)
Graphic presentations Current waveform is displayed with a resolution of 0,1 ms
Internal memory
Internal memory Up to 500 test results (including numerical and graphical data)
Power supply
Input 90 V - 264 V AC 50/60 Hz
Input power 250 VA
Display
Size 20 characters by 4 Lines
Type LCD with backlight
Applicable Standards
Safety Installation / Overvoltage - Category II
Pollution - Degree 2
LVD 2014/35/EU (CE Conform)
Standard EN 61010-1
Electromagnetic compatibility Directive 2014/30/EU (CE conform)
Applicable standard - EN 61326-1
CAN/CSA-C22.2 No. 61010-1
Environmental Conditions
Operating temperature - 20 ºC to + 55 ºC / - 4 ºF to + 131 ºF
Storage & transportation - 40 ºC to + 70ºC / - 40 ºF to + 158 ºF
Humidity 0% - 95% relative humidity, non-condensing
PC Interface
PC Interface Yes, USB
Warranty
Warranty 3 years
Abmessungen und Gewicht
Abmessungen (W x H x D) 170 x 405 x 335 mm (6,7 x 16,0 x 13,2 in)
Gewicht 6.5 kg (14,3 lbs)
  • Coil supply cable set 2 x 5 m 2,5 mm2 with banana plugs
  • Analog channels cable set 4 x 5 m with banana plugs
  • Auxiliary contact cable 5 m with banana plugs
  • Cable bag (2pcs)
  • Ground (PE) cable
  • USB cable
  • CAT34 device
  • External trigger cable 5 m with banana plugs
  • Main contact cables 5 m with SCT clamps
  • Coil control cable 5 m with banana plugs (Three-pole control - 2 coil channels)
  • Jumper cable 1 x 30 cm 2,5 mm2 with banana plugs with retractable isolation (black) (3pcs)
  • Jumper cable 1 x 30 cm 2,5 mm2 with banana plugs with retractable isolation (red) (3pcs)
  • Mains power cable EU 10 A
  • Plastic transport case – small size
  • USB with DV-Win software
The DV-Win software provides the acquisition and analysis of the test result, as well as the complete control of the CAT Standard series functions from a PC. These test results can be overlayed and compared graphically and numerically. The test results can be viewed, edited, saved, printed and exported Selecting the measurement points and intervals using the two cursors Downloading the test results from the instrument Zoom and pan graph feature Ability to generate a report including all asset-related information and performed tests. This provides you with a comprehensive overview of the test object, test results and assessments.